HDJY-2000 series manual/automatic dosing device (pure water dosing)

HDJY-2000 series manual/automatic dosing device (pure water dosing)

Realize 24-hour continuous control throughout the day, with a control accuracy of 0 5% -1%  Can save more than 30% of medication usage 

Online customer service:

  • Product Introduction
  • Technical Parameter

introduction

This device consists of a metering pump, a dosing tank, a mixer, a liquid level gauge, a scale inhibitor, a safety valve, a pressure gauge, and an electrical control cabinet (including a frequency converter). This system has the characteristics of reasonable design, high automation, safe and reliable operation, and simple operation. Widely used in water treatment and dosing systems for power plant feedwater, boiler water, raw water, circulating cooling water, and industrial wastewater and sewage. Pure water dosing includes: ① adding ammonia to feedwater and condensate; ② Adding hydrazine to water supply; ③ Add phosphate to the furnace. All of the above are for furnace dosing. Raw water and other additives include: ① adding coagulants and coagulant aids to raw water (raw water); ② Circulating water with stabilizer (corrosion inhibitor), scale inhibitor, and mixed bacterial agent; ③ The condenser is coated with ferrous sulfate, all of which are added outside the furnace. This series of dosing devices has been applied in dozens of various types of units and other enterprises in China, and has been highly praised by users.

HDJY-2001 is for pure water dosing, and HDJY-2002 is for external wastewater dosing. (Optional)


Characteristics

Realize 24-hour continuous control with a control accuracy of 0.5% -1%.

Can save more than 30% of medication usage.

Automatic monitoring and control, saving manpower.

The monitoring system can achieve networking.

Adopting computer control, the software design is flexible and can achieve various reports to meet the requirements of different users.

Advanced intelligent fuzzy regulation, output standard 4-20mA regulation signal and complete control unit composed of frequency converter.

Equipped with various control methods such as manual, automatic, and soft manual. Maximize the satisfaction of on-site requirements.

For different medicinal liquids, automatic dispensing and stirring can be achieved through a PLC system.

The solution tank, metering pump, system pipeline, and control system of the dosing device are centrally arranged to form a compact small unit structure, which is convenient for the design department's design and daily maintenance of users.

The solution tank, metering pump, and system pipeline prepared by the dosing device are all designed with anti-corrosion measures as needed. The main components in the control system are all products from internationally renowned companies.

The control system is equipped with functions such as electrical protection, low liquid level alarm, and automatic pump stop at low liquid level.

The data adopts Samsung's storage technology from South Korea, greatly increasing the amount of data. It can store tens of thousands of sets of measurement data and 5000 system operation records (known as the 5000 notepad function).

Application: In the fields of chemical engineering, fertilizer, metallurgy, etc. in thermal power plants, as well as in situations where (20~170) L/h boiler water, circulating internal cold water, industrial pure water, wastewater, and sewage are added with chemicals


ModelAmmonia dosingHDJY-2001AAdding hydrazineHDJY-2001BAdding phosphateHDJY-2001C
Container Capacity(0.5~2)m3(0.5~2)m3(0.5~2)m3
Tank materialstainless steelstainless steelstainless steel
Pump typeMechanical diaphragm pumpMechanical diaphragm pumpHydraulic diaphragm pump
total power(1~2.4)MPa(1~2.4)MPa(5.0~24)MPa
total power(3~6)KW  2 boxes and 3 pumps
Mixer configuration380V、960PRM、power(0.37~1.2)KW


Standard configuration

combinationOne box with one pump, one box with two pumps, two boxes with two pumps, two boxes with three pumps, two boxes with multiple pumps, etc. (determined according to the dosing point) -2001A
Medicine box materialsCarbon steel, stainless steel, fiberglass, and PE fiberglass
Container Capacity(1×0.5、2×0.5、1×1.0、2×1.0、2×2.0、1×5.0、1×10.0)m2(quantity × volume)
Mixer configuration380V、960PRM、power0.37-0.74KW
Measurement pump configurationSelect a metering pump based on dosage, medium type, and system pressure
Pump typeMechanical diaphragm pump
External dimensions(1800×850×1900及2900×1100×2200)mm (wide × high × deep)
Weight(2~5)t


classificationnameModelUnit set combination formTank volume(m3Technical parameters of the pumpelectric load(KW)load(t)
flow(L/H)pressure(MPa)power(KW)
Raw water dosingFlocculant adding deviceHDJY-2002AOne box with two pumps or two boxes with two pumps1~250~1000.32~1.00.55&1.53~82.5~5
Alkaline adding device215~4000.8~2.00.75&1.5
Adding coagulant aid device1~25~10000.32~1.00.55&1.5
Circulating water dosingCirculating water corrosion inhibitor deviceHDJY-2002BTwo boxes, two pumps, one box, two pumps, two boxes, three pumps1~2 1~350~700.37~1.00.55~1.53~82~6
Circulating water scale inhibitor device
3.60.151.5
Circulating water and sterilization device
Boiler start-up layer dosingAmmonia dosing deviceHDJY-2001AOne box with two pumps0.5~120~501.60.37 0.5532.5
Phosphate addition deviceTwo boxes and three pumps4.2~6.30.55 0.754
Coating of condenserCondenser coating deviceHDJY-2002COne box, one pump1~32~40.435~62~5
Two boxes and two pumps10~113~7.5