Button start: Set the "on/off/automatic" position on the control panel to the "on" position, and the equipment will run; Press to the "stop" position, the device stops.
Touch screen manual: Set the "on/off/automatic" position on the control panel to the "automatic" position, and set the control interface of the touch screen to the "manual" position. Click the control button below to start and stop the corresponding device.
Local automatic preparation: Set the "on/off/automatic" control panel to the "automatic" position, and set the touch screen control interface to the "automatic" position. At the same time, set the "Local/Stop/Remote" on the control panel to the "Local" position, then click to go to the start position. The preparation system runs automatically. When the liquid level is high, the system stops preparing. Restore preparation when the liquid level drops below. When there is no medicine in the hopper, there will be an audible and visual alarm prompt. It is necessary to feed the hopper through a vacuum feeder.
Remote automatic preparation: Set the "on/off/automatic" position on the control panel to the "automatic" position, and set the control interface of the touch screen to the "automatic" position. At the same time, set the "Local/Stop/Remote" on the control panel to the "Remote" position to remotely start the device through communication.
When the dosing pump is in manual mode, the equipment is started and stopped by a knob, and the speed is adjusted by a potentiometer. In the "local" control mode of the touch screen, start and stop the device through buttons. Enter the frequency in the input box for speed regulation. In remote mode, start and stop the dosing pump through Ethernet communication, and set the frequency remotely.